Turns per volt and wire area

Enter frequency, flux density, core area, voltages, regulation, currents, and current density. AWG and EI tables are not used.

Winding
Wire and window
Auxiliary estimate

C = 1.15 is the CRGO silicon-steel constant only if you enter it. It does not replace Ac.

Worked example

Turns per volt 4.6922 /V

TPV = 1 / (4.44 * f * Bmax * Ac * 10^-4)

Primary

Primary turns 1079.2042

Np = Vp * TPV

Primary wire area 0.1667 mm2

Area mm2 = current / J

Primary ohms 2665.6589 ohm

Zp / Zs = (Np / Ns)^2

Secondary

Secondary turns 59.1216

Ns = Vs * TPV * (1 + regulation)

Secondary wire area 2.6667 mm2

Area mm2 = current / J

Fill factor 28.1271

Kw = (Np * Ap + Ns * As) / window

Kw is above 0.38.

Estimated Ac 1.6263 cm2

Ac = C * sqrt(VA / f)

This is not approval to build a mains power supply. Insulation, temperature rise, and safety are not checked.

1.15 is the CRGO silicon-steel constant only if you enter it. The 2.5 to 3.5 A/mm2 range is a note, not a stored row.